| 2004-03-02 00:00:00 | *********** PROVISO/REVISION ****** | | | | | | 1)NOTE: PLEASE CORRELATE VOLTAGE, ONE | | | SHOWS 208V AND THE OTHER 240V. | | | | | | 2)NOTE: PLEASE CORRELATE FEEDERS, ONE | | | SHOWS #1 AND THE OTHER NOTE MENTIONS | | | #1/0'S | | | | | | 3)NOTE: PLEASE SEE MIN LOAD FOR LAUNDRY | | | TO BE 1500 VA. 220.16 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|