2004-03-02 00:00:00*********** PROVISO/REVISION ******
  
 1)NOTE: PLEASE CORRELATE VOLTAGE, ONE
 SHOWS 208V AND THE OTHER 240V.
  
 2)NOTE: PLEASE CORRELATE FEEDERS, ONE
 SHOWS #1 AND THE OTHER NOTE MENTIONS
 #1/0'S
  
 3)NOTE: PLEASE SEE MIN LOAD FOR LAUNDRY
 TO BE 1500 VA. 220.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  