| Plan Review Notes For Permit 04010578 |
| Permit Number |
04010578 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-30 00:00:00 | PROVISO: | | | 1.CONDENSING UNIT STAND SHALL COMPLY | | | WITH 2001 FBC 1511.7, SEE THE SCHEDULE | | | BELOW FOR PROPER HEIGHT REQUIREMENT. | | | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3.A SEPARATE DRAIN IS REQUIRED | | | FROM THE AUXILIARY DRAIN PAN TERMINATING | | | AT A CONPICUOUS POINT TO SERVE AS AN | | | ALARM THAT THE PRIMARY DRAIN IS | | | RESTRICTED.A FLOAT SWITCH MAY BE USED | | | IN LIEU OF SEPARATE DRAIN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|