Plan Review Notes
Plan Review Notes For Permit 04010577
Permit Number 04010577
Review Stop P
Sequence Number 2
Notes
Date Text
2004-03-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 CAST IRON SOVENT DESIGN MAN.
 NUMBER 802
  
 1) WATER HAMMER ARRESTORS LOCATED AT
 KITCHEN SINK SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN.
  
 2) SHT P-2 SANITARY RISER DIAGRAM FOR
 THE BATHROOM GROUPS. SOVENT DESIGN CALLS
 FOR A PRL LINE TO CONNECT TO THE VERTIC-
 AL PORTION OF THE STACK DOWNSTREAM OF
 THE OFFSET. A DE-AERATOR FITTING WILL BE
 REQUIRED AS SHOWN IN ATTACHED SHEET WITH
 PRL LINE TIED INTO IT.
  
 REVIEW BY KEN STEVENS