| Plan Review Notes For Permit 04010577 |
| Permit Number |
04010577 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-25 00:00:00 | ********* PROVSIO ***** | | | | | | 1)NOTE: PLEASE SEE 220.16, LOAD FOR | | | LAUNDRY CIRCUIT STILL NOT SHOWN AS REQ'D | | | 1500VA. | | | | | | 2)NOTE: PLEASE CORRELATE FEEDER CONDUCT- | | | -OR SIZES. ONE NOTE MENTIONS, 1/0'S | | | OTHER MENTIONS #1'S. | | | | | | PLEASE SUBMIT THE ABOVE AS A REVISION | | | BEFORE ANY ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|