2004-01-14 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE PLANS/ PANELS
 AND LOAD CALCULATIONS. SEE ITEMS SHOWN
 ON PANELS THAT ARE BEING DELETED.
  
 2)NOTE: PLEASE SEE BOTH PANELS SHOWN AS
 A-2.
  
 3)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS. PER 210.12
  
 4)NOTE: PLEASE SEE 220.16B FOR MIN LOAD
 REQ'D FOR LAUNDRY CIRCUIT.
  
 5)NOTE: PLEASE HAVE ARCH "SIGN" PLANS
 WITH A FULL "SIGNATURE" PER FS 481.221
 MIN SIGNATURE TO CONTAIN A VISABLE FIRST
 AND LAST NAME AS SHOWN ON LICENSE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.