| Plan Review Notes For Permit 04010575 |
| Permit Number |
04010575 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-14 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE CORRELATE PLANS/ PANELS | | | AND LOAD CALCULATIONS. SEE ITEMS SHOWN | | | ON PANELS THAT ARE BEING DELETED. | | | | | | 2)NOTE: PLEASE SEE BOTH PANELS SHOWN AS | | | A-2. | | | | | | 3)NOTE: PLEASE LIST THE REQ'D ARC FAULT | | | PROTECTED CIRCUITS. PER 210.12 | | | | | | 4)NOTE: PLEASE SEE 220.16B FOR MIN LOAD | | | REQ'D FOR LAUNDRY CIRCUIT. | | | | | | 5)NOTE: PLEASE HAVE ARCH "SIGN" PLANS | | | WITH A FULL "SIGNATURE" PER FS 481.221 | | | MIN SIGNATURE TO CONTAIN A VISABLE FIRST | | | AND LAST NAME AS SHOWN ON LICENSE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|