| Plan Review Notes For Permit 04010575 |
| Permit Number |
04010575 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT:04010575 | | | ADD: 1805 N FLAGLER DR# 315 | | | CONT: G C WORKS INC | | | TEL: (305)861-2918 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)PLANS TO BE SIGNED WITH FULL SIGNATURE | | | FROM THE ARCH PER FL S S 481.221 WITH | | | THE MINIMUM OF FIRST & LAST NAMES AS | | | SHOWN ON ARCH LICENSE. FAC 61G1-16.003 | | | | | | 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 3)104.2.1.3 THE BUILDING OFFICIAL | | | MAY SET STANDARDS THROUGH DEPARTMENTAL | | | POLICY STANDARDS FOR PLANS AND SPRCIFICA | | | TIONS. "NO WHITE OUT". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|