Plan Review Notes
Plan Review Notes For Permit 04010574
Permit Number 04010574
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-14 00:00:00********** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE NEW PLANS W/
 PANEL SCHEDULES AND LOAD CALCS.
 PANELS STILL SHOW ITEMS THAT WILL NO
 LONGER BE PLANS OR IN-USE.
 BOTH PANELS ARE LABELD AS "A-2".
  
 2 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12 2002 NEC
  
 3)NOTE: PLEASE SEE 220.16B FOR MIN LOAD
 REQ'D FOR LAUNDRY. SHOWN AS 1200 VA
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 NOTE: PLEASE SIGN PLANS WITH A COMPLETE
 "SIGNATURE"
 FS 481.221
 HOW SIGNATURE APPEARS ON LICENSE/SEAL.