Plan Review Notes
Plan Review Notes For Permit 04010573
Permit Number 04010573
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-14 00:00:00************** UNSAT ************
  
 1)NOTE: PERMIT APPLICATION WAS SUBITTED
 WITH THE ADDRESS IF 1803 N FLAGLER,
 COMES UP IN COMPUTER FOR THAT PCN AS
 1801. PLEASE ADJUST.
  
 2)NOTE: PLEASE CORRELATE PLANS AND PANEL
 SCHEDULES. PLEASE SEE THAT THERE ARE
 MANY ITEMS THAT ARE BEING REMOVED.
 PLEASE ALSO ADJUST LOAD CALCUALTIONS.
  
 3 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
  
 4)NOTE: PLEASE SIGN PLANS WITH LEGAL
 SIGNATURE. APPEARS TO BE INITIALS.
 WE HAVE BEEN GIVEN NOTICE THAT PLANS
 MUST CONTAIN COMPLETE SIGNATURE AS ON
 LICENSE. FS 481.221 AND FAC 61G1-16
  
 5)NOTE: PLEASE SEE BOTH PANELS LABELED
 AS "A-2".
  
 6)NOTE: PLEASE SEE 220.16B FOR MIN
 LAUNDRY LOAD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  