Plan Review Notes
Plan Review Notes For Permit 04010566
Permit Number 04010566
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-10 00:00:00DENIED
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 2.FBC3401.7.2.6 PROJECT VALUE OVER
 50%OF THE IMPROVED VALUE OF THE
 BUILDING.
 EXISTING STRUCTURE TO COMPLY WITH THIS
 SECTION OF THER CODE
 3.FBC 1006.2.2 AND 1006.2.4 EXTERIOR
 STAIRS SHALL COMPLY WITH THIS SECTION OF
 THE CODE. 1 HOUR SEPERATION REQUIRED
 ON THIS WALL INCLUDING ALL PENATRATIONS
 WITHIN 10 FT AS MENTIONED IN THE CODE.
 4.FBC 1608.2.2 GAURDRAILS SHALL COMPLY
 WITH THIS SECTION AND HAVE A 200LB.
 CONCENTRATED LOAD.
 5. CHECK SIZE AND DEPTH OF EXISTING
 FOOTING AND VERIFY THEY WILL MEET THE
 ADDITIONAL LOAD.SHOW DETAIL.
 6.NO PRODUCT APPROVALS SUBMITTED.
 SUBMIT 2 COPIES OF PRODUCT APPROVALS.
 7.SHOW SIZE AND TYPE OF DRYWALL USED
 ON GARAGE CEILING.
 8.WINDOW BUCK DETAIL (11) SHOULD
 COMPLY WITH 1707.4.4.2 BUCK SHALL EXTEND
 BEYOND THE INTERIOR FACE OF THE WINDOW
 OR DOOR FRAME.TO PROVIDE FULL SUPPORT
 OF THE FRAME.
 9.SHOW STAIRS ON SITE PLAN.
 10.VERIFY MEAN ROOF HEIGHT.SHOWN AS
 30FT.
  
 ANY QUESTIONS CALL
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672