Date Text
2004-04-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
  
 A) COMMENTS FROM PREVIOUS REVIEW. NUMBER
 TO STAY THE SAME TO AVOID CONFUSION.
 3) SHTS ME4 & ME6 PLUMBING PLAN FIRST
 FLOOR AND SANT. RISER DIAGRAM. WATER
 CLOSET P-2 IN MEN'S ROOM NOT VENTED.
 SECTION 901.2.1. - RESPONSE NOTED, BUT
 THE P-2 W/C VENTED WAS IN THE WOMENS
 TOILET ROOM. P-2 IN MEN'S TOILET ROOM IS
 DOWNSTREAM OF THE SANITARY LINE FROM THE
 2ND FLOOR AND HAS NO VENT TO DRAW FROM.
 8) EMERGENCY OVERFLOW DRAINS HAVE BEEN
 DELETED AND OVERFLOW SCUPPERS ARE SHOWN.
 PROVIDE A DETAIL OF THE OVERFLOW SCUPPER
 (TYPICAL) AND SHOW HEIGHT & WIDTH. MIN.
 38 SF REQUIRED. SHOW COMPLIANCE WITH
 SECTION 1511.6.4.3 (BUILDING) & SECTION
 1107.3 (PLUMBING)
 *****NEW COMMENT***
 1B) SHT ME6 WATER HEATER DETAIL - P/T
 RELIEF VALVE DISCHARGE LINE SHALL NOT
 HAVE ANY TRAPPED SECTIONS, AND SHALL
 HAVE A VISIBLE AIR GAP OR AIR GAP FITT-
 ING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER.
  
 REVIEW BY KEN STEVENS