| Plan Review Notes For Permit 04010540 |
| Permit Number |
04010540 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-04-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | | | | A) COMMENTS FROM PREVIOUS REVIEW. NUMBER | | | TO STAY THE SAME TO AVOID CONFUSION. | | | 3) SHTS ME4 & ME6 PLUMBING PLAN FIRST | | | FLOOR AND SANT. RISER DIAGRAM. WATER | | | CLOSET P-2 IN MEN'S ROOM NOT VENTED. | | | SECTION 901.2.1. - RESPONSE NOTED, BUT | | | THE P-2 W/C VENTED WAS IN THE WOMENS | | | TOILET ROOM. P-2 IN MEN'S TOILET ROOM IS | | | DOWNSTREAM OF THE SANITARY LINE FROM THE | | | 2ND FLOOR AND HAS NO VENT TO DRAW FROM. | | | 8) EMERGENCY OVERFLOW DRAINS HAVE BEEN | | | DELETED AND OVERFLOW SCUPPERS ARE SHOWN. | | | PROVIDE A DETAIL OF THE OVERFLOW SCUPPER | | | (TYPICAL) AND SHOW HEIGHT & WIDTH. MIN. | | | 38 SF REQUIRED. SHOW COMPLIANCE WITH | | | SECTION 1511.6.4.3 (BUILDING) & SECTION | | | 1107.3 (PLUMBING) | | | *****NEW COMMENT*** | | | 1B) SHT ME6 WATER HEATER DETAIL - P/T | | | RELIEF VALVE DISCHARGE LINE SHALL NOT | | | HAVE ANY TRAPPED SECTIONS, AND SHALL | | | HAVE A VISIBLE AIR GAP OR AIR GAP FITT- | | | ING LOCATED IN THE SAME ROOM AS THE | | | WATER HEATER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|