2004-01-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT DETAIL FOR DRINKING FOUNTAIN
 PER SECTION 11-4.15 AND ALL SUBSECTIONS.
 2) SUBMIT DETAIL FOR BREAK ROOM SINK PER
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 3) SHTS ME4 & ME6 PLUMBING PLAN FIRST
 FLOOR AND SANT. RISER DIAGRAM, WATER
 CLOSET P-2 IN MEN'S ROOM NOT VENTED.
 SECTION 901.2.1
 4) SHT ME4 WATER HEATER UNDER SINK SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL. SECTION
 501.4
 5) SHT ME6 AN RPZ BACKFLOW IS REQUIRED
 ON WATER SERVICE. SECTION 608.13.2
 6) SHT ME6 WATER ISOMETRIC, SHOW WATER
 HEATER PAN DRAIN LINE FOR W/H IN BATH-
 ROOM. SECTIONS 504.8.1 & 504.8.2.
 7) SUBMIT A STORM RISER DIAGRAM SHOWING
 PIPE SIZES AND TERMINATION ECT. SECTION
 104.3.1.1
 8) SHT 7.1 CLAIRFY 5" ERD"S.
 9) SUBMIT CALCULATIONS FOR PRIMARY ROOF
 DRAINS. INDICATE SQUARE FOOTAGE OF ROOF
 AND 1/2 AREA OF ALL VERTICAL WALLS IN-
 CLUDING PARAPETS IN CALCULATIONS. SECT-
 IONS 1106 & 1107 AND ALL SUBSECTIONS.
  