| Plan Review Notes For Permit 04010540 |
| Permit Number |
04010540 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-29 00:00:00 | DENIED: | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 403.3. | | | | | | 2.PLEASE INDICATE WHAT THE WAREHOUSE | | | WILL BE USED FOR.PROVIDE INFORMATION | | | ON ANY CHEMICALS OR COMBUSTIBLES THAT | | | MAY BE STORED. | | | | | | 3.PLANS DO NOT INDICATE VENTILATION | | | FOR THE WAREHOUSE AREA.SHOW COMPLIANCE | | | WITH 2001 FBC(M) TABLE 403.3 FOR | | | MINIMUM VENTILATION REQUIREMENTS. | | | | | | 4.DUCT SMOKE DETECTORS REQUIRED IN THE | | | SUPPLY DUCT OF SYSTEMS WITH THE DESIGN | | | CAPACITY GREATER THAN 2,000 CFM. | | | PLEASE INDICATE DUCT SMOKE DETECTORS ON | | | THE PLAN. | | | | | | 5.PLEASE INDICATE CONDENSATE FOR THE | | | ROOF TOP UNITS THAT SERVE THE SECOND | | | FLOOR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|