Plan Review Notes For Permit 04010540
Permit Number 04010540
Review Stop M
Sequence Number 1
Notes
Date Text
2004-01-29 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 2.PLEASE INDICATE WHAT THE WAREHOUSE
 WILL BE USED FOR.PROVIDE INFORMATION
 ON ANY CHEMICALS OR COMBUSTIBLES THAT
 MAY BE STORED.
  
 3.PLANS DO NOT INDICATE VENTILATION
 FOR THE WAREHOUSE AREA.SHOW COMPLIANCE
 WITH 2001 FBC(M) TABLE 403.3 FOR
 MINIMUM VENTILATION REQUIREMENTS.
  
 4.DUCT SMOKE DETECTORS REQUIRED IN THE
 SUPPLY DUCT OF SYSTEMS WITH THE DESIGN
 CAPACITY GREATER THAN 2,000 CFM.
 PLEASE INDICATE DUCT SMOKE DETECTORS ON
 THE PLAN.
  
 5.PLEASE INDICATE CONDENSATE FOR THE
 ROOF TOP UNITS THAT SERVE THE SECOND
 FLOOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.