| Plan Review Notes For Permit 04010540 |
| Permit Number |
04010540 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-16 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED | | | PRIOR TO, DURING AND AFTER | | | CONSTRUCTION. | | | | | | 2) A KNOX-BOX WILL BE REQUIRED. | | | | | | 3) PLEASE ILLUSTRATE ON PLANS ALL | | | EMERGENCY LIGHT FIXTURE LOCATIONS | | | FOR SECOND FLOOR. | | | | | | 4) FIRE WATER LINES SHOULD BE LOOPED | | | WHENEVER POSSIBLE. IT APPEARS THAT | | | THE 6" WATER MAIN ON SITE FOR THIS | | | PROJECT DEAD-ENDS NEAR THE WAREHOUSE. | | | | | | 5) PLEASE EXPLAIN WHY STAIR # 201 DOES | | | NOT HAVE A DOOR AT THE TOP OR BOTTOM | | | AND WHY IS IT OPEN TO THE SECOND FLOOR. | | | | | | 6) PLEASE INDICATE INTERIOR FINISH | | | FOR WALLS AND CEILINGS. | | | | | | 7) NO FIRE SPRINKLER PLANS PROVIDED. | | | | | | 8) IT WAS ALSO NOTED THAT FUTURE | | | EXPANSIONS ARE PLANNED, IS THE | | | PLANNED WATER FIRE LINE GOING TO BE | | | BIG ENOUGH. | | | | | | 9) PLEASE PROVIDE MORE DETAILS ON 3/4 | | | HOUR RATED OPENING PROTECTIVES ON | | | SOUTH ELEVATION. | | | | | | 10) TACTILE SIGNAGE REQUIRED AT STAIR | | | LOCATIONS. | | | | | | 11) ELEVATOR WARNING SIGNS REQUIRED | | | AT ELEVATOR. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|