| 2004-01-22 00:00:00 | ************ UNSAT *********** |
| | |
| | ** PLANS ONLY IN FOR PLAN REVIEW AND NOT |
| | FOR PERMIT*** |
| | |
| | 1)NOTE: PLEASE PROVIDE A BRIEF LOAD |
| | SUMMARY FOR W/SQ FT KVA LOAD FOR A/C |
| | SYSTEMS. PER 220CALL FOR INFO. |
| | |
| | 2)NOTE: PLEASE SHOW/CLARIFY NEW REQ'D |
| | SIGN CIRCUIT PER 600.5 |
| | |
| | 3)NOTE: PLEASE CLARIFY LOCATION OF GFI |
| | RECEPT FOR COND UNITS. PER 210.63 |
| | ROOF TOP ALSO. |
| | |
| | 4)NOTE: PLEASE CLARIFY/ SHOW METHOD |
| | OF EQUIPMENT GROUNDING FOR ALL FEEDERS/ |
| | CONDUITS ON RISER DIAGRAM. 250.110, |
| | 250.24 ETC. SIZE PER 250.122 |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | MAIN NOT SHOWN. NOTED FOR PANELS. |
| | |
| | 6)NOTE: PLEASE SEE FIRE REVIEW COMMENTS, |
| | AND COMMENTS FROM OTHER REVIEWERS AS |
| | THEY MAY OR MAY NOT HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | 7)NOTE: PLEASE REMOVE ALL OLD/ VOIDED |
| | SHEETS AND INSERT NEW SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | SOME REVIEWERS REQUIRE ONE SET OF OLD |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |