| 2004-03-09 00:00:00 | | | | BUILDING REVIEW COMMENTS | | | -------- ------ -------- | | | | | | 1] | | | PROVIDE SOILS INVESTIGATION REPORT, 2 | | | COPIES SIGNED AND SEALED. | | | | | | 2] | | | SUBMIT ALL PRODUCT APPROVAL REPORTS FOR | | | EXTERIOR WINDOWS, DOORS, GLAZING, ROOF | | | AND WALL COVERINGS. | | | | | | 3] | | | PROVIDE SIGNED AND SEALED FIRE | | | SPRINKLER DESIGN AND LAYOUT ACCORDING | | | TO: FBC 104.3.1.1#5 | | | | | | 4] | | | SHEET 10.1 WINDOW SCH.-WN1 REFERENCES | | | 110MPH WIND SPEED. FBC REQUIRES DESIGN | | | TO 140MPH. | | | | | | 5] | | | CHECK DOOR SCH. #122 AND #202 SHALL BE | | | 3/4HR RATED PER FBC 1006.2.2 | | | | | | 6] | | | SHEET S-6,NOTES ACI 318-94 SHALL BE | | | ACI 318-02 PER FBC CHAPTER 35. | | | SHEET S-6 SHALL BE SIGNED AND DATED BY | | | ENGINEER. | | | | | | | | | | | | | | | | | | LUIS MARTINEZ | | | 561-805-6710 |
|