| 2004-01-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A-4 DETAIL 2/A-4A SHOW CLEAR |
| | FLOOR SPACE FOR URNAL PER SEC 11-4.18.3 |
| | 2) SHT A-4 DETAIL 5/A-4 LOUNGE SINK. |
| | SHOW KNEE CLEARANCE 11-4.24.3, CLEAR |
| | FLOOR SPACE 11-4.24.5, & EXPOSED PIPES |
| | AND SURFACES 11-4.24.6. |
| | 3) SHT A-5 DETAILS 2/A-5, & 3/A-5, SHOW |
| | HEIGHT OF W/C 11-4.16.3, AND ACCESSIBLE |
| | LAV TO BE CENTERED MIN. 15" OFF WALL. |
| | 4) SHT A-5 DETAIL 7/A-5 IF DRINKING |
| | FOUNTAIN IS NOT A HIGH LOW, THEN PROVIS- |
| | IONS SHALL BE MADE FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING PER SEC. |
| | 11-4.1.3(10)(A). |
| | 5) SHT P-1 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL REQUIRED PER SEC. |
| | 607.3.2. |
| | 6) SHT P-1 PLUMBING NOTES #'S 1 & 2 |
| | REFER TO STANDARD CODE. THE CODE ADOPTED |
| | AND IN EFFECT IS THE FLORIDA BUILDING |
| | CODE PLUMBING. PLEASE CHANGE REFERENCE. |
| | 7) SUBMIT A SANITARY RISER DIAGRAM AND A |
| | WATER RISER DIAGRAM FOR THE NEW LOUNGE |
| | SINK PER SEC. 104.3.1.1 |
| | 8) SHT P-1 DOMESTIC WATER RISER DIAGRAM, |
| | WATER HAMMER ARRESTORS AT FIXTURE P-4 |
| | SHALL BE LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. PDI-WH 201 & MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | |