| Plan Review Notes For Permit 04010527 |
| Permit Number |
04010527 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-15 00:00:00 | 1) IS IT CORRECT TO HAVE DOOR 301 SWING | | | INWARD. THIS OFFICE COUNTED OVER 40 | | | SEATS BUT IT IS NOT CLEAR IF ANY SEATS | | | WERE OMITTED FROM THE DRAWING. IF 50 | | | OR MORE PERSONS CAN OCCUPY 307, THEN | | | THIS EXIT ACCESS DOOR 301 SHOULD | | | SWING IN THE DIRECTION OF EXIT TRAVEL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|