Plan Review Notes
Plan Review Notes For Permit 04010493
Permit Number 04010493
Review Stop E
Sequence Number 7
Notes
Date Text
2005-09-04 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE CORRELATE PLANS WITH
 RISER DIAGRAM SUBMITTED.
 PLEASE SEE CABANNA SHOWS A J-BOX WHEN
 RISER SHOWS A PANEL?
 PLEASE SEE 225.31-225.36, WHICH REQUIRES
 A MEANS OF DISCONNECT AT DETACHED BLDGS.
 PLEASE SEE EXCEPTS ALLOW SP SWITCHES FOR
 MIN CIRCUITS.
 PLEASE PROVIDE THE AMOUNT OF CIRCUITS
 AND SEE 250.32 WHICH STILL REQUUIRES THE
 GROUNDING ELECTRODE SYSTEM WITH MORE
 THAN ONE CIRCUIT.
 PLEASE SEE 240.24, WHICH DOES NOT ALLOW
 OCP IN BATH RMS.
  
 SPOKE TO HOME-OWNER ABOUT THE PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  