| Notes |
| Date |
Text |
| 2005-09-04 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLEASE CORRELATE PLANS WITH | | | RISER DIAGRAM SUBMITTED. | | | PLEASE SEE CABANNA SHOWS A J-BOX WHEN | | | RISER SHOWS A PANEL? | | | PLEASE SEE 225.31-225.36, WHICH REQUIRES | | | A MEANS OF DISCONNECT AT DETACHED BLDGS. | | | PLEASE SEE EXCEPTS ALLOW SP SWITCHES FOR | | | MIN CIRCUITS. | | | PLEASE PROVIDE THE AMOUNT OF CIRCUITS | | | AND SEE 250.32 WHICH STILL REQUUIRES THE | | | GROUNDING ELECTRODE SYSTEM WITH MORE | | | THAN ONE CIRCUIT. | | | PLEASE SEE 240.24, WHICH DOES NOT ALLOW | | | OCP IN BATH RMS. | | | | | | SPOKE TO HOME-OWNER ABOUT THE PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|