Plan Review Notes
Plan Review Notes For Permit 04010493
Permit Number 04010493
Review Stop P
Sequence Number 5
Notes
Date Text
2004-07-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SANT. RISER DIAGRAM DOES NOT MEET THE
 CODE REQUIREMENTS, NOR DOES IS REFLECT
 THE FLOOR PLAN.
 - THE CABANA BATH SHOWS TWO LAVS, ONLY
 ONE LAV ON THE FLOOR PLAN. ALSO THE BAR
 SINK IS NOT SHOWN ON THE RISER DIAGRAM.
 THE BAR SINK SHALL NOT DISCHARGE THRU
 THE HORIZONTAL WET VENT FOR THE BATHROOM
 FIXTURES. SECTIONS 104.2.1 & 909,1
 - THE MASTER BATH MAXIMUM NUMBER OF
 FIXTURE UNITS FOR A 2" WET VENT IS 4.
 THE WET VENT FOR THE MASTER BATH HAS 6.
 TABLE 909.3
 - THE WASH MACHINE SHOWN ON THE FLOOR
 PLAN IS NOT SHOWN ON THE RISER DIAGRAM.
 SECTION 104.2.1
 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025 - THIS IS
 NOT SHOWN ON ONE RISER DIAGRAM AND THE
 ENGINEERS NAME IS NOT ON THE OTHER RISER
 DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved