Plan Review Notes
Plan Review Notes For Permit 04010493
Permit Number 04010493
Review Stop E
Sequence Number 4
Notes
Date Text
2004-06-21 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE ORIG PLANS CALLED OUT
 AN EXISTING 200A PANEL. NEW SHEET SHOWS
 ANEW 200A PANEL.
 PLEASE SHOW LOCATION OF METER.
 NO MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S INSIDE HOUSE. 230.70
  
 2)NOTE: PLEASE SHOW/ INDICATE MAIN AND
 AIC RATING OF NEW MAIN. 110.9/215.5
  
 3)NOTE: PLEASE SHOW GROUNDING PER 250.50
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  