| Plan Review Notes For Permit 04010493 |
| Permit Number |
04010493 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-06-21 00:00:00 | **** UNSAT **** | | | | | | 1)NOTE: PLEASE SEE ORIG PLANS CALLED OUT | | | AN EXISTING 200A PANEL. NEW SHEET SHOWS | | | ANEW 200A PANEL. | | | PLEASE SHOW LOCATION OF METER. | | | NO MORE THAN 8' OF UNPROTECTED CONDUCTOR | | | -S INSIDE HOUSE. 230.70 | | | | | | 2)NOTE: PLEASE SHOW/ INDICATE MAIN AND | | | AIC RATING OF NEW MAIN. 110.9/215.5 | | | | | | 3)NOTE: PLEASE SHOW GROUNDING PER 250.50 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANYQUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|