Plan Review Notes
Plan Review Notes For Permit 04010493
Permit Number 04010493
Review Stop P
Sequence Number 3
Notes
Date Text
2004-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA STATUTES
  
 1) SHT A-1 SANITARY RISER DIAGRAM. LAV
 STILL NOT SHOWN ON VENT LINE FOR SHOWER
 & TUB. ANOTHER LAV LINE WAS DRAWN IN AND
 THAT LEAVES THE VENT LINE FOR THE TUB &
 SHOWER A DRY HORIZONTAL VENT WHICH IS
 NOT APPROVED. SECTION 905.3
 2) PER FLORIDA STATUTES ALL HAND DRAWN
 CORRECTIONS TO A SIGNED AND SEALED SET
 OF PLANS SHALL BE DATED AND INITIALED BY
 THE ENGINEER OF RECORD.
  
 REVIEW BY KEN STEVENS