| Plan Review Notes For Permit 04010493 |
| Permit Number |
04010493 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-05-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA STATUTES | | | | | | 1) SHT A-1 SANITARY RISER DIAGRAM. LAV | | | STILL NOT SHOWN ON VENT LINE FOR SHOWER | | | & TUB. ANOTHER LAV LINE WAS DRAWN IN AND | | | THAT LEAVES THE VENT LINE FOR THE TUB & | | | SHOWER A DRY HORIZONTAL VENT WHICH IS | | | NOT APPROVED. SECTION 905.3 | | | 2) PER FLORIDA STATUTES ALL HAND DRAWN | | | CORRECTIONS TO A SIGNED AND SEALED SET | | | OF PLANS SHALL BE DATED AND INITIALED BY | | | THE ENGINEER OF RECORD. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|