| Plan Review Notes For Permit 04010493 |
| Permit Number |
04010493 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-05-08 00:00:00 | **** NOTES REDLINED **** | | | | | | 1)NOTE: FOOTER STEEL REQ'D TO BE BONDED | | | AT EACH DEATCHED BLDG. GARAGE AND | | | DETACHED CABANA.250.50,250.32 | | | | | | 2)NOTE: RECEPT ADDED FOR REQ'D PENIN- | | | -SULAR TO BE GFI/GFI PROTECTED PER | | | 210.8A6. | | | | | | 3)NOTE: RECEPT FOR 2'OF WALL IN BR | | | 210.52. | | | | | | THE ABOVE IS NOTED AND REDLINED ON PLANS | | | THERE IS NO NEED TO CORRECTIONS OR TO | | | REVISE PLANS AT THIS TIME. | | | | | | IF THERE ARE OTHER CHANGES IN SCOPE OF | | | WORK OR OTHER REVISIONS DURING CONSTRUCT | | | -ION, PLEASE MAKE THE ABOVE CHANGES AT | | | THAT TIME BEFORE SUBMITTING REVISIONS. | | | | | | IF THERE THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|