| 2004-04-18 00:00:00 | ************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE DETACHED CABANA IS |
| | SHOWN HAVING INDIVIDUAL CIRCUITS FEEDING |
| | BLDG. PLEASE SEE 225.31, 250.32. |
| | A MCB SUB PANEL IS REQ'D FOR THIS INSTA- |
| | -LLATION. PLEASE SHOW ON RISER DIAGRAM |
| | AND SUBMITTED REVISED PANEL SCHEDULES |
| | ACCORD. |
| | |
| | 2)NOTE: PLEASE SEE 210.52C 1,2,3,, ETC |
| | FOR RECEPT SPACING IN KITCHEN. |
| | PENINSULAR AREA IS REQ'D TO HAVE RECEPTS |
| | PER 210.52C3,5 |
| | |
| | 3)NOTE: PLEASE SEE PANEL "A" IS SHOWING |
| | 100AFEED NEW SUB PANEL "B" WITH #12 |
| | AND 20A BRKR?? PLEASE CORRELATE WITH |
| | LOAD ON PANEL, OCP ETC. 310.16, 240 |
| | 2002 NEC |
| | |
| | 4)NOTE: PLEASE SEE FS 471.025 AND FAC |
| | 61G15-23.002. ALL SETS OF PLANS ARE |
| | REQ'D TO BE ORIG SIGNED,DATED AND SEALED |
| | BY ENGINEER OF RECORD. ONE SET IS MISS- |
| | -ING THIS. |
| | |
| | 5)NOTE:PLEASE SEE ATTACHED COPY OF FS |
| | 553.80(2)(B). THIS IS ONLY A NOTICE TO |
| | DESIGNER. PLEASE ADDRESS THESE COMMENTS |
| | AS SOME ARE THE SAME AS FIRST REVIEW. |
| | |
| | 6)NOTE: PANEL SCHEDULES INDICATE AHU/A/C |
| | UNITS BEING INSTALLED. HOWEVER UNITS |
| | NOT SHOWN ON PLANS. PLEASE SHOW. PLEASE |
| | ALSO SHOW DISC'S PER 440.11, RECEPTS PER |
| | 210.63 AND IF ATTIC ETC INSTALLATION, |
| | LTS ETC PER 210.70 |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |