| Plan Review Notes For Permit 04010493 |
| Permit Number |
04010493 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMIN. CODE | | | FLORIDA STATUTES | | | | | | 1) SHT A-5 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS, NOR DOES IT | | | REFLECT THE FLOOR PLAN. | | | A. MASTER BATH LAV'S ARE NOT VENTED. | | | B. TRAP REQUIRED ON TUB. 1002.1 | | | C. VENT REQUIRED BETWEEN TUB AND SHOWER | | | D. KITCHEN SINK & WASH MACHINE SHALL | | | NOT DISCHARGE INTO WET-VENTED HORIZONTAL | | | BRANCH OF THE BATHROOM FIXTURES. 909.1 | | | E. KITCHEN SINK & WASH MACHINE ARE DOWN | | | STREAM OF BATHROOM FIXTURES. - (SEE EX- | | | AMPLE OF RISER DIAGRAM THAT MEETS CODE | | | REQUIREMENTS AND REFLECTS THE FLOOR PLAN | | | ATTACHED TO COMMENTS. | | | 2) WHERE IS SANITARY RISER DIAGRAM FOR | | | THE NEW CABANA? | | | 3-ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. FAC 61G15-23.002(2) & FS 471.025 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|