| 2004-01-20 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | |
| | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SHOW COMPLIANCE WITH 250.32 & |
| | 225.31,DISCONNECTS AND GROUNDING, FOR |
| | BOTH OF THE SEPERATE STRUCTURES. |
| | |
| | 2} PLESSE CONFIRM THA THE NEUTRAL FEEDER |
| | TO THE NEW PANEL WILL BE 3/0 AS SHOWN |
| | ON PLANS. |
| | |
| | 3} PLEASE SUBMIT A PANEL SCHEDULE FOR |
| | PANEL "B" SHOWING NEW CIRCUITS. |
| | |
| | 4} INDICATE THE TYPE OF CONDUIT FROM |
| | PANEL "A" TO PANEL "B", SHOW COMPLIANCE |
| | WITH 210.122 IF APPLICABLE. |
| | |
| | 5} INDICATE COMPLIANCE WITH 210.8(A)(2) |
| | IN THE GARAGE.(REQ'D GFI). |
| | |
| | 5} PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 6} PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5,IF WIRING IS BEING |
| | REPLACED. PLANS FAIL TO INDICATE |
| | WHETHER NEW OR EXISTING. |
| | |
| | 7} PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 8} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BERATED FOR THE AVAILABLE FAULT |
| | CURRENT.PER 110.9/215.5. |
| | |
| | 9} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |