2004-01-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SHOW COMPLIANCE WITH 250.32 &
 225.31,DISCONNECTS AND GROUNDING, FOR
 BOTH OF THE SEPERATE STRUCTURES.
  
 2} PLESSE CONFIRM THA THE NEUTRAL FEEDER
 TO THE NEW PANEL WILL BE 3/0 AS SHOWN
 ON PLANS.
  
 3} PLEASE SUBMIT A PANEL SCHEDULE FOR
 PANEL "B" SHOWING NEW CIRCUITS.
  
 4} INDICATE THE TYPE OF CONDUIT FROM
 PANEL "A" TO PANEL "B", SHOW COMPLIANCE
 WITH 210.122 IF APPLICABLE.
  
 5} INDICATE COMPLIANCE WITH 210.8(A)(2)
 IN THE GARAGE.(REQ'D GFI).
  
 5} PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 6} PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5,IF WIRING IS BEING
 REPLACED. PLANS FAIL TO INDICATE
 WHETHER NEW OR EXISTING.
  
 7} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 8} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT.PER 110.9/215.5.
  
 9} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]