| 2004-02-12 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 3)1609.4.3 LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| | MORE LOADS IN COMBINATION WITH DEAD LOAD |
| | ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| | 1609.4.1 OR 1609.4.2, THE COMBINED |
| | EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| | FROM THE LOAD COMBINATION OF THE DEAD |
| | LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| | EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| | CIFIED IN THE MATERIALS SECTIONS OF THIS |
| | CODE OR A REFRENCED STANDARD SHALL NOT |
| | BE USED WITH THESE LOAD COMBINATIONS |
| | EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH |
| | CHAPTER 23. |
| | REVISE TRUSS ANCHOR SCHEDULE USING |
| | VALUES THAT DO NOT INCLUDE THE ONE- |
| | THIRD INCREASE. TRUSS ANCHORS ARE |
| | REQUIRED TO HAVE STATE OR LOCAL PRODUCT |
| | APPROVAL. |
| | |
| | 4)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) SUBMIT STATE OR LOCAL PRODUCT |
| | APPROVAL IN ACCORDANCE WITH RULE 9B-72, |
| | FOR THE BUTT GLASS WINDOW. SPECIFY THE |
| | TYPE OF GE SILCONE TO BE USED. THE |
| | HEIGHT DIMENSION ON THE PLAN IS NOT |
| | CONSISTANT. |
| | |
| | 6) THE COLLIER GARAGE DOOR REQUIRES |
| | STATE OR LOCAL PRODUCT APPROVAL IN |
| | ACCORDANCE WITH RULE 9B-72, INCLUDING |
| | QUALITY ASSURANCE. SUBMIT FORM FOR LOCAL |
| | PRODUCT APPROVAL. THE SIZE LIMITATION IN |
| | THE ENGINEERED DRAWINGS EXCLUDE THE |
| | SMALLER GARAGE DOOR SHOWN ON THE PLANS. |
| | |
| | 7) SUBMIT THE APPROVED ENGINEERING AND |
| | INSTALLATION INSTRUCTIONS FOR THE ENTRY |
| | DOOR. |
| | |
| | 8) SPECIFY THE MOUNT TYPE AND ANCHORS |
| | THAT WILL BE USED FOR THE STORM PANELS. |
| | |
| | 9) SUBMIT STATE OR LOCAL PRODUCT |
| | APPROVAL FOR THE TRUSS ANCHORS THAT ARE |
| | SPECIFIED ON THE PLANS. |
| | |