| Plan Review Notes For Permit 04010402 |
| Permit Number |
04010402 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-29 00:00:00 | PROVISO: | | | PLANS DO NOT INDICATE IF THE AHU'S ARE | | | NEW OR EXISTING. | | | | | | NEW AHU OR AHU WITH NEW DUCTWORK SHALL | | | HAVE THE DUCT SMOKE DETECTOR INSTALLED | | | IN THE SUPPLY AIR DUCT AS REQUIRED PER | | | 2001 FBC(M) 606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|