| Plan Review Notes For Permit 04010359 |
| Permit Number |
04010359 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-06-16 00:00:00 | ************ UNSAT ********** | | | | | | PLEASE SEE NOTES FROM PREVIOUS TWO | | | REVIEWS. | | | | | | 1)NOTE: PLEASE SEE A SEPARATE 8 1/2X 11 | | | SHEET IS NOW BEING SUBMITTED SHOWING | | | A DIFFERENT RISER. | | | PLANS STILL DO NOT SHOW OR INDICATE IF | | | THIS NOW EXSITNG 60A SUB PANEL IS | | | LOCATED AT THIS DEATCHED GARAGE? | | | RISER NOW SHOWS THIS "EXISTING" 60A SUB- | | | -PANEL FEEDING A COTTAGE. | | | NO EQUIPMENT GRNDS ARE SHOWN, NO GROUND- | | | -ING ELECTRODE? PANEL SCHEDULE AND LOAD | | | FOR ADDED LOAD OF COTTAGE. | | | 215.5,225.31,250.32, ETC | | | PLEASE SUBMIT A RISER TO MEET CODE AND | | | CORRELATE WITH INFORMATION AS REQUESTED | | | ON PREVIOUS REVIEWS. | | | | | | PLEASE SEE COPY OF FS 553.80(2)(B) NOW | | | ATTACHED W/ RESPECT TO DESIGN PROFESSION | | | -AL. IF COMMENTS ARE NOT ADDRESS A 4X | | | FEE SHALL BE ACCESSED. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | AS OF TODAYS DATE, ARCH/DESIGNER OF | | | RECORD AHS NOT CONTACTED MYSELF WITH | | | ANY QUESTIONS OR CLARIFICATION WHAT IS | | | NEEDED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|