Plan Review Notes
Plan Review Notes For Permit 04010359
Permit Number 04010359
Review Stop E
Sequence Number 3
Notes
Date Text
2004-06-16 00:00:00************ UNSAT **********
  
 PLEASE SEE NOTES FROM PREVIOUS TWO
 REVIEWS.
  
 1)NOTE: PLEASE SEE A SEPARATE 8 1/2X 11
 SHEET IS NOW BEING SUBMITTED SHOWING
 A DIFFERENT RISER.
 PLANS STILL DO NOT SHOW OR INDICATE IF
 THIS NOW EXSITNG 60A SUB PANEL IS
 LOCATED AT THIS DEATCHED GARAGE?
 RISER NOW SHOWS THIS "EXISTING" 60A SUB-
 -PANEL FEEDING A COTTAGE.
 NO EQUIPMENT GRNDS ARE SHOWN, NO GROUND-
 -ING ELECTRODE? PANEL SCHEDULE AND LOAD
 FOR ADDED LOAD OF COTTAGE.
 215.5,225.31,250.32, ETC
 PLEASE SUBMIT A RISER TO MEET CODE AND
 CORRELATE WITH INFORMATION AS REQUESTED
 ON PREVIOUS REVIEWS.
  
 PLEASE SEE COPY OF FS 553.80(2)(B) NOW
 ATTACHED W/ RESPECT TO DESIGN PROFESSION
 -AL. IF COMMENTS ARE NOT ADDRESS A 4X
 FEE SHALL BE ACCESSED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
 AS OF TODAYS DATE, ARCH/DESIGNER OF
 RECORD AHS NOT CONTACTED MYSELF WITH
 ANY QUESTIONS OR CLARIFICATION WHAT IS
 NEEDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]