Plan Review Notes
Plan Review Notes For Permit 04010359
Permit Number 04010359
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-23 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE PROVIDE RISER DIAGRAM
 WITH FEED TO DETACHED STRUCTURE.
 EXISTING RISER DOES NOT SHOW ANY INFOR-
 -MATION ON HOW BLDG WILL BE FED.
 CONDUITS/CONDCUTORS/ GROUNDING/ PANEL
 DISC MEANS. ETC .
 225.31,250.32,215.5 ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 REVIEW. A RESUB FEE WILL NOT BE DUE.