2004-03-08 00:00:00PROVISO:
 THE TRANSFER AIR GRILLE FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 INTO THE MASTER SUITE (INCLUDE BATHROOM)
 FOR A "TOTAL" OF SUPPLY AIR.TRANSFER
 IS TO BE SIZED 50 SQ IN TO 100 CFM OF
 SUPPLY AIR.PLEASE SIZE ACCORDINGLY.
  