| Date |
Text |
| 2004-01-22 00:00:00 | ***************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | SHOWN FOR PANEL , NOT FOR MAIN. |
| | |
| | 2)NOTE:SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | MISSING INSIDE BEDROOMS. |
| | |
| | 3 )NOTE: PLEASE SHOW /CLARIFY METHOD |
| | OF THE EQUIPMENT GROUNDING BETWEEN |
| | MAIN MEANS OOF DISC AND PANELS/GUTTERS. |
| | 250.110,250.24 |
| | PLEASE SIZE ALL EQUIPMENT GROUNDING |
| | CONDUCTORS PER 250.122 |
| | |
| | 4)NOTE; PLEASE SHOW SEC'S ON RISER TO |
| | WEATHERHEAD. |
| | |
| | 5)NOTE: PLEASE SEE NOTES BELOW RISER/ |
| | PANEL SCHEDULE. SHOWS CITY OF FT LAUDER- |
| | -DALE. PLEASE ADJUST TO CITY OF WPB. |
| | |
| | 6)NOTE: PLEASE VERIFY SIZE OF PANEL, |
| | SHOWN AS 42 CIR, AND 150A. PLEASE SEE |
| | IF 150A PANELS ARE MADE AS 42 CIR. |
| | |
| | 7)NOTE: PLEASE SEE THE FOLLOWING IS ONLY |
| | AN FYI NOTE: IF THERE IS GOING TO BE |
| | ANY LV IN HOUSE(TV/PHONE) ETC. PLEASE |
| | SHOW ON PLANS, OR SEPARATE PLANS WILL |
| | BE REQ'D AT LATER DATE. |
| | SEPARATE LV PERMIT WILL BE REQ'D. |
| | |
| | 8)NOTE: PLEASE PROVIDE ALL LICENSE #'S |
| | ON TITLE BLOCK AS REQD' UNDER FS/ FAC |
| | PLEASE ALSO SIGN WITH A MIN OF A VISABLE |
| | FIRST AND LAST NAME AS SHOWN ON SAID |
| | SEAL. IT HAAS BEEN TRANSLATED TO THIS |
| | OFFICE THAT INITAILS ARE NOT PERMITTED. |
| | 481.221, 61G1-16.004 |
| | SIGNATURE WOULD NEED TO MATCH LICENSE |
| | SIGNED W/ STATE. |
| | 481.221, |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |