| Plan Review Notes For Permit 04010279 |
| Permit Number |
04010279 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-13 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | 1. STATE PRODUCT APPROVALS REQUIRED FOR | | | THE HURRICANE SHUTTERS ON EXISTING | | | WINDOWS (RE: #1 GENERAL NOTES) | | | 2. NO ELECTRIC SHOWN ON PLANS.IF | | | THERE IS ELECTRIC A SEPARATE PERMIT IS | | | REQUIRED WITH DRAWINGS. | | | 3. FLORIDA PRODUCT APPROVALS REQUIRED | | | FOR THE GLASS BLOCK. | | | 4. NEED DETAILS FOR THE WALL FILLING IN | | | ABOVE THE PRIVACY WALL. | | | 5. SHEETS 1-4 ARE NOT SEALED BY ENGINEER | | | WHO SIGNED THEM. PER FL. STATUTES PLANS | | | MUST BE SEALED BY ARCH. OR ENG. SIGNING | | | PLANS. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|