| Plan Review Notes For Permit 04010269 |
| Permit Number |
04010269 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-22 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE 1/0 FEEDER FROM THE METER TO THE | | | PANEL IS NOT SUFFICIENT FOR 200 AMPS.SEE | | | 310.15(B). | | | | | | 2} THERE ARE FOUR SMALL APPLIANCE | | | CIRCUITS SHOWN ON THE LOAD CALCS | | | (6000/1500=4),BUT ONLY THREE ON THE | | | PANEL SCHEDULE, PLEASE CORRELATE. | | | | | | 3} THE DINING ROOM & MORNING ROOM WIRE | | | SIZE MUST BE #12 PER 210.52(B)(1).SEE | | | PANEL SCHEDULE. | | | | | | 4} THE WATER HEATER AND DRYER LOADS IN | | | THE CALCULATION DOES NOT CORRESPOND | | | WITH THE PANEL SCHEDULE.PLEASE | | | CORRELATE. | | | | | | 5} BATH #2 IS MISSING A RECEPTACLE,SEE | | | 210.52(D). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|