| Date |
Text |
| 2004-02-12 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04010269 |
| | ADD: 10775 LA STRADA |
| | CONT: A R CUSTOM HOMES INC |
| | TEL: (561)718-4176 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL I |
| | S NOT DEFINITEY KNOWN, OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL P |
| | ROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. SOILSREPORT NOT AN ORIGINAL |
| | SEAL.PLANS SPECIFICATIONS REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 3) PROVIDE 2 CURRENT COPIES OF SIGNED & |
| | SEALED SURVEYS WITH PROPOSED IMPROVEMENT |
| | TO BE COMPLETED. |
| | |
| | 4) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG FOR |
| | MORE INFORMATION. |
| | THIS APPROVAL SYSTEM IS ALSO REQUIRED |
| | FOR STRAPS, BUCKETS, AS WELL AS WINDOWS, |
| | DOORS, SHUTTERS, ETC... |
| | |
| | 5)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THE TRUSS ANCHOR SCHEDULE IS UNREADABLE! |
| | PLEASE STREACH THE LETTERING OUT SO IT |
| | DOESN'T OVERLAP! |
| | |
| | 6) STORM SHUTTERS REPORT MISSING THE |
| | INSTALLATION INSTRUCTIONS SEE LIMITA- |
| | TIONS 9.1/9.2. |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 7) SUBMIT GARGE INSTALLATION SCHEDULE |
| | FOR THE DOOR TO BE USED. THIS WILL DES- |
| | IGNATE PRESSURE ZONES. |
| | |
| | 8)905.2.1 APPROVED SINGLE-STATION OR |
| | MULTIPLE STATION SMOKE DETECTORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH NFPA 72, |
| | CHAPTER 2, WITHIN EVERY DWELLING UNIT |
| | WITHIN AN APARTMENT HOUSE, CONDOMINIMUM, |
| | OR TOWNHOUSE AND EVERY GUEST OR SLEEPING |
| | ROOM IN A MOTEL, HOTEL, OR DORMITORY & |
| | SLEEPING ROOMS IN RESIDENTIAL CARE/ |
| | ASSISTED LIVING OCCUPANCIES. WHERE MORE |
| | THAN ONE DETECTOR IS REQUIRED TO BE |
| | INSTALLED WITHIN INDIVIDUAL DWELLING |
| | UNIT, THE DETECTOR SHALL BE WIRED IN |
| | SUCH A MANNER THAT THE ACTUATION OF ONE |
| | ALARM WILL ACTIVATE ALL THE ALARMS IN |
| | THE INDIVIDUAL UNIT. |
| | THE SMOKE ALARMS LOCATED IN THE HALL- |
| | WAY RARE TO BE LOCATED NOT LESS THAN |
| | 5'-0" AWAY FROM THE RETURN AIR, SEE |
| | MANUFACTURER'S SPEC. |
| | |
| | 9) FL BLD CODE 2309.6 ATTIC ACCESS, PRO- |
| | VIDE ATTIC ACCESS 20"X36". INDICATE ON |
| | PLAN THE MINIMUM SIZE. |
| | |
| | 10)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |