| Plan Review Notes For Permit 04010266 |
| Permit Number |
04010266 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-14 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | ON THE PLANS FOR CODE COMPLIANCE. | | | | | | 1} THE 1/0 FEEDER FROM THE METER TO THE | | | PANEL IS NOT LARGE ENOUGH FOR 200 | | | AMPS.SEE 310.15(B)(6). | | | | | | 2} THERE ARE 4 SMALL APPLIANCE CIRCUITS | | | SHOWN IN THE LOAD CALCS (6000/1500=4) | | | BUT ONLY 3 IN THE PANEL SCHEDULE,PLEASE | | | CORRELATE. | | | | | | 3} THE DINING ROOM & MORNING | | | (BREAKFAST)ROOM WIRE SIZE LISTED ON THE | | | SCHEDULE | | | MUST BE # 12 PER210.52(B)(1),SMALL APP. | | | | | | 4}THE RANGE CALCULATION MUST COMPLY WITH | | | 220.19.8KW MIN. | | | | | | 5} THE OCP @60 AMPS IS TOO LARGE FOR THE | | | #8 WIRE FOR THE RANGE LISTED ON THE | | | PANEL SCHEDULE PER310.16. | | | | | | 6} THE GARAGE RECEPTACLES DO NOT COMPLY | | | WITH 210.8(A)(2),GFI. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|