| Date |
Text |
| 2004-01-12 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE NOTE, ALL PLANS DRAWN |
| | BY AN ARCHITECT/ENGINEER CONTAIN- |
| | -ING A TITLE BLOCK: MUST BE SIGNED, |
| | DATED AND SEALD BY THAT ARCH/ENG. |
| | PER FS 481.221 471.025 |
| | FAC 61G15-23.002, 61G1-16.004 |
| | SIGNATURE MUST BE ORIGINAL ALONG WITH |
| | DATE. |
| | |
| | 2 )NOTE: PLEASE INCLUDE ALL LICENSE |
| | #'S ON THE REQ'D TITLE BLOCK. |
| | PLEASE ALSO INCLUDE CERTIFICATE OF |
| | AUTHORIZATION #'S WHERE REQ'D. |
| | ARCH'S/ENGINEERS. |
| | PER FS 471.023, FAC 61G15-23.002 (ENG'S) |
| | PER FS 481.219, FAC 61G1-16.004 (ARCH'S) |
| | |
| | 3)NOTE: PLEASE SEE FIRE REVIEW NOTES, |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EM/EXT LTS. |
| | |
| | 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 5)NOTE: PLEASE CLARIFY IF PANELS ARE |
| | NEW OR EXSITING? SHOWN AS NEW. IF NEW |
| | PLEASE SHOW INFORMATIONWHERE AND HOW |
| | THESE PANELS ARE BEING FED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |