| 2004-02-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04010207 |
| | ADD: 1475 CENTREPARK # 301 |
| | CONT: LEIGHTON & MCGINN |
| | TEL: (561)722-9696 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | SIGNATURES ARE TO BE ORIGINALS SEE "E" |
| | PAGES, COPIED. |
| | |
| | 2) 905.1.5, PLEASE PROVIDE INFORMATION |
| | FOR EMERGENCY LIGHTING AND ALARMS. |
| | |
| | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 4) TENANT SEPERATION WALL, "M" PAGES |
| | INDICATE MEDIUM PRESSURE DUCT THROUGH |
| | TENANT SEPERATION WALLS? RATING? FIRE- |
| | DAPPERS! |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |