| Plan Review Notes For Permit 04010177 |
| Permit Number |
04010177 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-12 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} PLEASE PROVIDE A LOAD CALCULATION | | | INCLUDING EXISTING AND ALL ADDED LOADS | | | PER 215.5. | | | | | | 2} PROVIDE A RISER DIAGRAM INDICATING | | | FEEDER TO NEW PANEL,AND GROUNDING PER | | | 250.32. | | | | | | 3} SHOW LOCATION OF NEW PANEL ON PLAN. | | | | | | 4} BATH RECEPTACLE MUST BE GFI PER | | | 210.8(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|