| Plan Review Notes For Permit 04010138 |
| Permit Number |
04010138 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE AND CURRENT PRODUCT | | | APPROVAL FOR DOORS, WINDOWS, MULLIONS, | | | GLASS BLOCK, ROOF TILE AND ALL THE | | | STRUCTURAL CONNECTORS UNDER A SEPARATE | | | PERMIT AS REQ'D BY THE BLDG OFFICIAL. | | | 2-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | DWG #2 DON'T MATCH. REVISE AS REQ'D. | | | 3- CLARIFY/REVISE TRUSS ANCHOR SCHEDULE. | | | 4-TYP. WALL SECTION. CLARIFY WHERE ARE | | | TABLES 6 AND 8 COMING FROM? SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 5-SHEET #7: A)REVISE DESIGN PRESSURES | | | SHOWN ON REAR ELEVATION. | | | B)WINDOWS TO MATCH WINDOW SCHEDULE. | | | C)ALL NOTES ON FLOOR PLAN AND ROOF FRA- | | | MING PLAN TO REFLECT BEAM CHANGE FROM | | | WOOD TO CONCRETE. | | | 6- SHEET #3: CLARIFY NOTE REGARDING THE | | | UPLIFT CALCS AND CONNECTORS SELECTED. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|