| Plan Review Notes For Permit 04010131 |
| Permit Number |
04010131 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-06 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE CURRENT PRODUCT | | | APPROVAL FOR ALL DOORS, WINDOWS, ROOF | | | TILE, MULLIONS, GLASS BLOCK, AND ALL | | | STRUCTURAL CONNECTORS UNDER A SEPARATE | | | PERMIT. | | | 2-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | DWG #2 DON'T MATCH. REVISE AS REQ'D. | | | 3-CLARIFY/REVISE TRUSS ANCHOR SCHEDULE. | | | 4-TYPCIAL WALL SECTION DETAIL A/4: | | | CLARIFY WHERE ARE TABLES 6 AND 8 FOR | | | ROOF TILE FASTENERS TAKEN FROM?. SEE | | | SEC. 1606.3 FBC 2001 & SEC. 104.2.1.1 | | | CITY AMENDMENTS TO FBC 2001. | | | 5-SHEET #7:A)REVISE DESIGN PRESSURES. | | | B)WINDOWS ON REAR ELEVATION DON'T MATCH | | | THOSE ON WINDOW SCHEDULE. | | | C)REVISE AL NOTES ON FLOOR PLAN AND ROOF | | | FRAMING PLAN TO REFLECT CHANGE OF WOOD | | | BEAM TO CONCRETE BEAM. | | | 6-SHEET #3: CLARIFY NOTE REGARDING THE | | | UPLIFT CALCS AND CONNECTORS SELECTED. |
|