| Date |
Text |
| 2004-01-16 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-ARCHITECT TO COMPLY WITH CHAPTER 481 |
| | FLORIDA STATUTES WHEN SUBMITTING PLANS |
| | FOR PUBLIC RECORDS. |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR ALL DOORS/WINDOWS |
| | TYPE, MULLIONS, GLASS BLOCK ROOF TILE, |
| | STRUCTURAL CONNECTORS. |
| | 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR |
| | FIRE RATED GLASS BLOCK ASSEMBLY AND |
| | REVISE DETAIL TO MATCH IT. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| | DON'T MATC. CHECK SIZE OF FASTENER. |
| | 6-UPDATE TRUSS ANCHOR SCHEDULE. SEE SEC. |
| | 1609.4.3 FBC 2001. |
| | B)SPECIFY SIZE OF USP RT STRAP. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE. SEC. 104.2.1.1 CITY AMENDMENTS. |
| | 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 9-REVISE DESIGN PRESSURES. SEE TABLES |
| | 1606.2B AND 1606.2E FOR SIZE AND |
| | LOCATION. PROVIDE CALCULATIONS FOR |
| | DIFFERENT DESIGN PRESSURES. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 10-PROVIDE ENGINEERING CALCS FOR SIMPSON |
| | EG-7 CONNECTOR. FASTENER SPECIFIED IS |
| | DIFFERENT FROM THAT PUBLISHED ON |
| | CATALOGUE. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |