| Plan Review Notes For Permit 04010101 |
| Permit Number |
04010101 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-09 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE CURRENT PRODUCT APPRO | | | VALS FOR ALL DOORS, WINDOWS, MULLIONS, | | | GLASS BLOCK, ROOF TILE AND ALL | | | STRUCTURAL CONNECTORS UNDER A SEPARATE | | | PERMIT AS REQ'D BY BUILDING OFFICIAL. | | | 2-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | DWG #2 DON'T MATCH. REVISE AS REQUIRED | | | 3-CLARIFY/REVISE TRUSS ANCHOR SCHEDULE. | | | 4-TYPICAL WALL SECTION A/4: CLARIFY | | | WHERE ARE TABLES 6 & 8 TAKEN FROM? | | | SEE SEC. 1606.3 FBC 2001 AND SECTION | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | 5-SHEET #7: A)REVISE/CLARIFY DESIGN PRE- | | | SURES SHOWN ON EXTERIOR ELEVATION. | | | B)WINDOWS SHOWN ON ELEVATION DON'T MATCH | | | WINDOW SCHEDULE. | | | C)REVISE ALL NOTES ON FLOOR PLAN AND | | | ROOF FRAMING PLAN REGARDING THE CHANGE | | | OF WOOD BEAM TO CONCRETE BEAM. | | | | | | 6-SHEET #3: CLARIFY NOTE REGARDING THE | | | UPLIFT CALCS AND CONNECTORS SELECTED. |
|