| Plan Review Notes For Permit 04010095 |
| Permit Number |
04010095 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-06 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-ARCHITECT TO PROVIDE INFORMATION IN | | | ALL DWGS AS REQUIRED BY CHAPTER 481 | | | FLORIDA STATUTES. | | | 2-PROVIDE COMPLETE CURRENT PRODUCT APPRO | | | VAL FOR ALL DOORS, WINDOWS, MULLIONS, | | | ROOF TILE, GLASS BLOCK AND ALL | | | STRUCTURAL CONNECTORS UNDER A SEPARATE | | | PERMIT. | | | 3-DETAIL E/4 AND RESIDENTAIL NOTES ON | | | DWG #2 DON'T MATCH. REVISE AS REQUIRED | | | 4-REVISE WINDOW BUCK DETAIL. SEE SEC. | | | 1707.4.4.2 FBC 2001. | | | 5-DWG #2: A)REVISE/CLARIFY TRUSS ANCHOR | | | SCHEDULE. | | | B)PROVIDE DETAILS & CALCS FOR HOLDOWNS | | | AS SPECIFIED ON NOTE ON SAME DRAWING. | | | 6-SPECIFY ROOF TILE FASTENERS. SECTION | | | 1606.3 FBC 2001 AND SEC. 104.2.1.1 | | | CITY AMENDMENTS TO FBC 2001. | | | 7-PROVIDE REVISED ROOF FRAMING PLAN THAT | | | SHOWS CHANGE OF WOOD BM TO MASONRY BM. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | 8-SHEET #3: CLARIFY NOTE REGARDING THE | | | UPLIFT CALCS AND CONNECTORS SELECTED. |
|