| 2004-01-28 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-SOME DRAWINGS ARE MISSING ALL THE |
| | INFORMATION REQUIRED BY THE ARCHITECT |
| | WHEN SUBMITTING PLANS FOR PUBLIC |
| | RECORDS. CHAPTER 481 FLORIDA STATUTES. |
| | 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR ALL DOORS,WINDOWS |
| | GLASS BLOCK, ROOF TILE, MULLIONS AND |
| | STRUCTURAL CONNECTORS. |
| | 3-DETAIL E/4 AND RESIDENTIAL NOTES ON |
| | DWG #2 DON'T MATCH. REVISE AS REQ'D. |
| | 4-REVISE WINDOW BUCK DETAIL ON SHEET #4. |
| | SEE SECTION 1707.4.4.2 FBC 2001 FOR |
| | PROPER BUCK INSTALLATION. |
| | 5-DWG #2:A)CLARIFY/REVISE TRUSS ANCHOR |
| | SCHEDULE. CHECK FOR TYPOS THAT CREATE |
| | SOME CONFUSION ON ANCHOR SPECS. |
| | B)NOTE BELOW TRUSS ANCHOR SCHEDULE CALLS |
| | FOR ENGINEER'S DETAILS AND CALCS FOR |
| | HOLD DOWN ANCHORS. WHERE ARE THEY. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 6-SPECIFY ROOF TILE FASTENER AS REQ'D |
| | BY SEC. 104.2.1.1 CITY AMENDMENTS TO |
| | FBC 2001. ALSO, SEE SEC. 1606.3 FBC. |
| | 7-CLARIFY/REVISE DESIGN PRESSURES FOR |
| | EXTERIOR OPENINGS. EG: CHECK WINDOW AT |
| | BEDROOMS #2 & #3 ACCORDING TO LOCATION |
| | AND SIZE OF WINDOW. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 8-PROVIDE ENGINEERING CALCS FOR SIMPSON |
| | EG7 CONNECTOR SINCE FASTENERS ARE NOT |
| | THE SAME AS TESTED AND PUBLISHED BY |
| | SIMPSON TO COMPLY WITH SEC. 1609.4.3 |
| | FBC 2001. |
| | 9-PROVIDE COMPLETE SPECS FOR (4)2X12 WD |
| | BEAM AT REAR PORCH. HOW IS IT NAILED |
| | TOGETHER, ETC.SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 10-SHEET 3#: CLARIFY NOTE: "UPLIFT FOR |
| | EACH TRUSS ARE MORE THAN THE MAXIMUM |
| | VALUE SHOWN FOR THE CONNECTOR SELECTED |