| Plan Review Notes For Permit 04010087 |
| Permit Number |
04010087 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-ARCHITECT TO PROVIDE ALL INFORMATION | | | IN ALL DWGS AS REQUIRED BY CHAPTER | | | 481 FLORIDA STATUTES. | | | 2-PROVIDE COMPLETE PRODUCT AND CURRENT | | | PRODUCT APPROVALS FOR ALL WINDOWS, | | | DOORS, MULLIONS, GLASS BLOCK, ROOF | | | TILE AND ALL STRUCTURAL CONNECTORS | | | UNDER A SEPARATE PERMIT. | | | 3-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | DWG #2 DON'T MATCH. REVISE AS REQUIRED | | | 4-REVISE WINDOW BUCK DETAIL. SEE SECTION | | | 1707.4.4.2 FBC 2001. | | | 5-DWG #2: A)REVISE/CLARIFY TRUSS ANCHOR | | | SCHEDULE. | | | B)PROVIDE ENGINERING DETAILS AND CALCS | | | AS SPECIFIED ON NOTE. | | | 6-SPECIFY ROOF TILE FASTENERS. SEE SEC. | | | 1606.3 FBC 2001 AND SEC. 104.2.1.1 | | | CITY AMENDMENTS TO FBC 2001. | | | 7-PROVIDE REVISED ROOF FRAMING PLAN | | | SHOWING MASONRY BEAM INSTEAD OF WOOD. | | | 8-SHEET #3: CLARIFY NOTE REGARDING THE | | | UPLIFT CALCS AND ANCHORS SELECTED. |
|