Plan Review Notes
Plan Review Notes For Permit 04010074
Permit Number 04010074
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-13 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5
  
 2} PLEASE SHOW ALL RECEPTACLES SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED PER 210.8A-6
  
 3} THE DRYER MUST BE CALCULATED PER 220.
 18.
  
 4} PLEASE CALCULATE A LAUNDRY LOAD PER
 220.16(B),5000VA.ADD TO LOAD CALC.
  
 5} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]