| Plan Review Notes For Permit 04010074 |
| Permit Number |
04010074 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-13 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT. | | | PER 110.9/215.5 | | | | | | 2} PLEASE SHOW ALL RECEPTACLES SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECTED PER 210.8A-6 | | | | | | 3} THE DRYER MUST BE CALCULATED PER 220. | | | 18. | | | | | | 4} PLEASE CALCULATE A LAUNDRY LOAD PER | | | 220.16(B),5000VA.ADD TO LOAD CALC. | | | | | | 5} PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|