| 2004-02-06 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) THE SURVEY HAS THE WRONG FLOOD ZONE |
| | LISTED. THE STRUCTURE IS IN A "B" FLOOD |
| | ZONE. SUBMIT A REVISED SURVEY. |
| | |
| | 4) THE MAXIMUM HEIGHT ALLOWED BY ZONING |
| | FOR THIS STRUCTURE IS 33 FEET FROM GRADE |
| | TO THE HIGHEST POINT OF THE ROOF. THE |
| | ELEVATIONS INDICATE THAT THE STRUCTURE |
| | EXCEEDS THIS. |
| | |
| | 5) SPECIFY THE MEAN ROOF HEIGHT OF THE |
| | STRUCTURE ON THE PLAN. THIS IS THE |
| | HEIGHT FROM FINISH GRADE TO THE AVERAGE |
| | HEIGHT OF THE HIGHEST ROOF WITH A PITCH. |
| | |
| | 6) A THREE STORY R3 STRUCTURE OF TYPE VI |
| | CONSTRUCTION IS REQUIRED TO BE SPRINKLED |
| | OR ONE HOUR PROTECTED. SEE FBC TABLES |
| | 500 AND 600. |
| | |
| | 7) PROVIDE DETAILS FOR THE THIRD FLOOR |
| | ATTIC AREA. PROVIDE A CROSS SECTION. |
| | INDICATE THE EXTERIOR AND INTERIOR |
| | FINISHES, FRAMING, INSULATION, FLOOR |
| | SHEATHING, CONNECTORS, ETC. INDICATE ON |
| | THE PLANS IF THE ROOM WILL BE CONDITION- |
| | ED SPACE(NOT INDICATED BY ENERGY CALCS). |
| | |
| | 8) PROVIDE A DETAIL OF THE END WALLS OF |
| | THE ATTIC ROOM. SHOW SIZE AND SPACING OF |
| | THE FRAMING, STRAPPING, HEADER SIZE, |
| | FRAMING FOR ARCH ABOVE THE WINDOW. |
| | |
| | 9) INDICATE ON THE PLANS THAT THE WALLS |
| | OF THE STAIRS TO THE THIRD FLOOR ARE |
| | INSULATED AND THE DOOR IS SOLID OR |
| | INSULATED AND WEATHER STRIPPED IF THE |
| | ATTIC ROOM IS NOT INSULATED. FBC CHAPTER |
| | 13. |
| | |
| | 10) SPECIFY THE SIZE OF THE BUTT GLASS |
| | WINDOW IN THE BREAKFAST ROOM. |
| | |
| | 11) STAIRS DO NOT COMPLY WITH FBC |
| | 1007.3.1 EXCEPTION (1). SUM OF TWO |
| | RISERS AND A TREAD EXCLUSIVE OF NOSING |
| | SHALL BE NOT LESS THAN 24"OR MORE THAN |
| | 25". |
| | |
| | 12) SPECIFY THE POSITIVE AND NEGATIVE |
| | WINDLOAD PRESSURES FOR EACH OF THE |
| | EXTERIOR OPENINGS. |
| | |
| | 13) THE FOUNDATION WALL SECTION ON SHEET |
| | 4 IS FOR A STEM WALL AND THE PLANS ARE |
| | FOR A MONOLITHIC SLAB. PLEASE REVISE. |
| | SEE SOILS REPORT FOR FOOTER RECOMMENDAT- |
| | IONS. |
| | |
| | 14) PROVIDE A CROSS SECTIONAL DETAIL OF |
| | THE COVERED ENTRY. |
| | |
| | 15) THE FOUNDATION WALL SECTION ON SHEET |
| | 4 SPECIFIES METAL ROOFING AND THE |
| | ELEVATION ON SHEET 2 SHOWS CEMENT TILE. |
| | PLEASE CORRECT. |
| | |
| | 16) SPECIFY THE SPACING OF THE 5/8" J- |
| | BOLTS ON THE GARAGE DOOR JAMB DETAIL ON |
| | SHEET 5. |
| | |
| | 17) THE WINDOW BUCK AND SILL DETAILS ON |
| | SHEET 5 SPECIFY 1X P.T. BUCKS AND THE |
| | TYPICAL WOOD BUCK TO CONCRETE DETAIL |
| | SPECIFIES 2X P.T. FOR WIDOW AND DOOR |
| | OPENINGS. PLEASE CLARIFY. SPECIFY THE |
| | SPACING OF THE T-NAIL FASTENERS. |
| | |
| | 18) SPECIFY THE UPLIFT VALUES FOR THE |
| | TRUSSES ON THE ROOF FRAMING PLANS ON |
| | SHEET 5. SPECIFY THE TRUSS CONNECTORS |
| | TO BE USED. |
| | |
| | 19) SPECIFY THE LIVE LOADS FOR THE ATTIC |
| | AREA AND THE ATTIC. SEE FBC TABLE 1604.1 |
| | |
| | 20) INDICATE THE SIZE AND LOCATION OF |
| | THE ATTIC ACCESS OPENING FOR THE ATTIC |
| | ABOVE THE THIRD FLOOR ATTIC ROOM. SEE |
| | FBC 2309.6. |
| | |
| | 21)SPECIFY ATTIC VENTILATION AS REQUIRED |
| | BY FBC 2309.7. |
| | |
| | 22) SPECIFY HOW THE WATERPROOFING OF THE |
| | BALCONY ABOVE THE GARAGE WILL BE |
| | ACCOMPLISHED. |
| | |
| | 23) PROVIDE A DETAIL OF THE CONCRETE |
| | BEAM OR LINTEL ABOVE THE GARAGE THAT |
| | SUPPORTS THE SECOND FLOOR AND ROOF. |
| | |
| | 24) PROVIDE DETAILS OF THE 2"X 12" BEAM |
| | THAT SUPPORTS THE FLOOR SYSTEM FOR THE |
| | SECOND STORY. SPECIFY LUMBER GRADE, NAIL |
| | SIZE & SPACING. GLUEING, ETC. INDICATE |
| | THE ATTACMENT OF BEAM AT EXTERIOR |
| | MASONRY WALLS AND ATTACHMENT OF FLOOR |
| | TRUSSES TO BEAM. |
| | |
| | 25) PROVIDE A DETAIL OF THE CANTILEVER |
| | CONCRETE BEAM ABOVE THE BUTT GLASS |
| | WINDOWS IN THE BREAKFAST ROOM. SPECIFY |
| | SIZES AND LOCATION OF STEEL REINFORCING, |
| | ETC. |
| | |
| | 26) SPECIFY ON THE PLANS THE LOCATIONS |
| | AND MATERIAL THAT WILL BE USED FOR THE |
| | DRAFTSTOPPING OF THE FLOOR/CEILING |
| | ASSEMBLY INTO AREAS OF NO MORE THAN 500 |
| | SQFT. SEE FBC 2305.2.2. |
| | |
| | 27) SPECIFY ON THE PLANS HOW THE BALCONY |
| | RAILS WILL BE ATTACHED TO THE STRUCTURE, |
| | THE HEIGHT OF THE RAIL AND THE SPACING |
| | OF THE INTERMEDIATE RAILS. SEE FBC 1015 |
| | AND 1608.2. SHOP DRAWINGS WILL BE |
| | REQUIRED. |
| | |
| | 28) SPECIFY THE DIAMETER AND LENGTH OF |
| | POWER ACTUATED FASTENERS USED TO ANCHOR |
| | THE BASE OF THE LOADBEARING INTERIOR |
| | WALL ON SHEET 3. |
| | |
| | 29) SPECIFY THE CONNECTORS AT THE TOP |
| | AND BOTTOM OF THE 4"X 4" POST AT THE |
| | STAIRS SUPPORTING THE SECOND FLOOR. |
| | |
| | 30)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. |
| | |
| | 31) SUBMIT (2) TWO COPIES OF ALL PRODUCT |
| | APPROVALS. SUBMIT PRODUCT APPROVALS FOR |
| | THE FOLLOWING: |
| | - BUTT GLASS WINDOWS IN THE BREAKFAST |
| | ROOM |
| | - BAY WINDOW IN THE GREAT ROOM |
| | - GREENHOUSE WINDOW |
| | - FRENCH DOORS WITHOUT SIDELITES |
| | - INSWING ENTRY DOOR WITH SIDELITE |
| | - OUTSWING DOOR AT GARAGE |
| | - ARCHED TOP CASEMENT WINDOWS |
| | |
| | 32) UNLESS ALL GLAZING IS IMPACT RESIST- |
| | ANT STORM PANELS WILL BE REQUIRED. |
| | SUBMIT PRODUCT APPROVALS, KEY PLAN AND |
| | INSTALLATION SCHEDULE FOR STORM PANELS |
| | IF USED. |
| | |
| | 33) WINDOWS IN THIRD FLOOR ATTIC ROOM |
| | MUST MEET EGRESS REQUIREMENTS OF FBC |
| | 1005.4. |
| | |
| | 34) THE OWNER/AGENT IS REQUIRED TO SIGN |
| | AND DATE THE ENERGY CALC. FORM. FBC |
| | CHAPTER 13. |
| | |
| | IN ORDER TO EXPEDIATE PLAN REVIEW, |
| | PLEASE SUBMIT OLD SHEETS WHEN RESUBMITT- |
| | ING NEW PLANS. |