| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE NOTE, ALL PLANS DRAWN |
| | BY AN ARCHITECT/ENGINEER CONTAIN- |
| | -ING A TITLE BLOCK: MUST BE SIGNED, |
| | DATED AND SEALED BY THAT ARCH/ENG. |
| | PER FS 481.221 471.025 |
| | FAC 61G15-23.002, 61G1-16.004 |
| | |
| | 2} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BERATED FOR THE AVAILABLE FAULT |
| | CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3} PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 4} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 5} PLEASE CORRECT NOTE #3 TO COMPLY WITH |
| | 210.8(A)(6), ALL COUNTERTOP RECEPTACLES |
| | |
| | 4} NOTE #4 INDICATING SMOKE DETECTOR |
| | BRANCH CIRCUITS DOES NOT INDICATE |
| | COMPLIANCE WITH 210.12. |
| | |
| | 5} THE REFERENCE TO LAKE WORTH UTILITY |
| | IN NOTE #6 IS INCORRECT. |
| | |
| | 6} NOTE # 7 IS AN INCORRECT REFERENCE. |
| | SEE 2002 NEC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |