| Plan Review Notes For Permit 04010039 |
| Permit Number |
04010039 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-ARCHITECT TO PROVIDE ALL HIS INFO IN | | | ALL DWGS AS REQUIRED BY CHAPTER 481 | | | FLORIDA STATUTES. | | | 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC | | | PRODUCT APPROVAL FOR DOORS, WINDOWS, | | | MULLIONS, GLASS BLOCK, ROOF TILE AND | | | ALL STRUCTURAL CONNECTORS UNDER A | | | SEPARATE PERMIT. | | | 3-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | DWG #2 DON'T MATCH. REVISE AS REQ'D. | | | 4-REVISE WINDOW BUCK DETAIL. SEE SECTION | | | 1707.4.4.2 FBC 2001. | | | 5-DWG #2: A)REVISE/CLARIFY TRUSS ANCHOR | | | SCHEDULE. | | | B)PROVIDE ENGINEER'S DETAILS AND CALCS | | | AS SPECIFIED ON NOTE. | | | | | | 6-SPECIFY ROOF TILE FASTENERS. SECTION | | | 1606.3 FBC 2001 & SEC. 104.2.1.1 CITY | | | AMENDMENTS TO FBC 2001. | | | 7-PROVIDE REVISED ROOF FRAMING PLAN | | | SHOWING CONCRETE BEAM INSTEAD OF WOOD | | | BEAM. SEC. 104..2.1.2 CITY AMENDMENTS. | | | 8-SHEET #3: CLARIFY NOTE REGARDING | | | UPLIFT AND CONNECTORS SELECTED. |
|