Plan Review Notes
Plan Review Notes For Permit 04010031
Permit Number 04010031
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-10 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 3)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 ON SHEET 9 THE VALUES FOR THE USP
 META 16 CONNECTOR IS TOO HIGH, IT IS
 LISTED IN USP CATALOG AS 1200#. THE
 VALUE OF THE SIMPSON META 16 IS LISTED
 IN THE HIGH WIND RESISTANT CONSTRUCTION
 CATALOG (WITHOUT STRESS INCREASE) AS
 1115#. THIS CHANGE WILL AFFECT THE ROOF
 GIRDER TRUSS REQUIRING 2356# OF UPLIFT.
 PLEASE CORRECT.
  
 4) THE DIMENSIONS LISTED ON THE BUTT
 GLASS DETAIL SHEET OF THE PLANS HAS
 DISCREPANCIES WITH THE SIZES OF THE
 GLASS PANELS AND THE SIZES SHOWN ON THE
 PLAN. INDICATE THE SPECIFIC G.E. SEALANT
 THAT IS TO BE USED (I.E. G.E. #1200).
 SUBMITTALS FOR WINDOWS ARE REQUIRED TO
 COMPLY WITH RULE 9B-72. PLEASE SUBMIT
 THE APPROPRIATE PRODUCT APPROVAL.
 PRODUCT APPROVALS FOR THE STOREFRONT
 FRAMES ARE ALSO REQUIRED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL. SEE
 ATTACHMENT AND WWW.FLORIDABUILDING.ORG.
  
 5) THE WINDLOAD PRESSURES FOR THE 2068
 DOOR TO BATH #2 ARE NOT LISTED ON THE
 ELEVATIONS. SUBMIT PRODUCT APPROVAL WITH
 INSTALLATION INSTRUCTIONS FOR THIS DOOR.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE 8070
 OVERHEAD GARAGE DOOR. THE PRODUCT
 APPROVAL SUBMITTED HAS A MINIMUM SIZE
 LIMIT OF 10'W X 6'H.
  
 7) THE PRODUCT APPROVAL FOR THE COLLIER
 GARAGE DOOR DOES NOT HAVE THE CORRECT
 SUBMITTAL FORM. THE PROPER FORM HAS BEEN
 ATTACHED. SEE RULE 9B-72.
  
 8) SUBMIT STATE PRODUCT APPROVALS FOR
 TRUSS CONNECTORS THAT WILL BE USED IN
 THIS STRUCTURE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714